某10kV全封闭隔离开关断裂故障失效分析
Failure Analysis of a 10 kV Fully Enclosed Isolation Switch
田博海 1李刚 1张丰丽 1贾海龙 1梁启军 1李卓玛吉 2张烁 1陈莲君 1李子彬 1韩梦龙1
作者信息
- 1. 国网青海省电力公司电力科学研究院,青海 西宁 810008
- 2. 国网青海省电力公司西宁供电公司,青海 西宁 8100083
- 折叠
摘要
利用化学成分检测、微观形貌检测、金相检测、力学性能检测及断口形貌分析等试验方法,对某10 kV全封闭隔离开关断裂原因进行了分析,得出该隔离开关转轴存在大量的气孔是断裂的主要原因.此外,为防止再次出现隔离开关断裂故障,提出了针对性的建议.
Abstract
The fracture reason of a 10 kV fully enclosed isolation switch was analyzed by means of chemical composition detection,microscopic morphology detection,metallographic detection,mechanical properties detection and fracture morphology analysis.It was concluded that the main reason for the fracture was the existence of a large number of pores in the rotating shaft of the switch.In addition,in order to prevent the failure of the isolation switch from happening again,specific suggestions are put forward.
关键词
隔离开关/断裂/铝合金/失效分析Key words
isolation switch/severance/aluminum alloy/failure analysis引用本文复制引用
出版年
2024