首页|一起换流变压器产气故障的分析与诊断

一起换流变压器产气故障的分析与诊断

Analysis and Diagnosis of A Gas Production Fault of Converter Transformer

扫码查看
介绍了一起换流变压器的典型运维检修案例.首先,对返厂后进行的常规试验、耐压试验、感应电压试验、长时空载试验和过电流试验等成品试验结果进行了分析,确定了换流变压器内部存在过热故障;然后,通过吊芯解体发现换流变压器铁芯存在片间短接情况和绕组存在烧熔现象,印证了之前的试验判断;最后,对该系列产品后续的工艺改进和出厂试验提出了几点建议.
A typical operation and maintenance case of converter transformer is introduced.Firstly,the conventional test,withstand voltage test,induced voltage test,long-time no-load test and overcurrent test are analyzed after the converter transformer being returned to the manufacturer,and it is determined that there exists overheating fault inside the converter transformer.And through the disassembly of hanging core,it is found that the core of converter transformer is short circuited between pieces and the winding is burnt,which confirms the previous test judgment.Finally,some suggestions are put forward for the following process improvement and factory test of this series of products.

converter transformerinduced voltage testlong-time no-load testovercurrent testdisassembly inspection

杨在葆、杨城、刘永、韩凯、伊峰、高志新

展开 >

山东电力设备有限公司,山东 济南 250022

大唐临清热电有限公司,山东 聊城 252600

国网山东省电力公司电力科学研究院,山东 济南 250003

换流变压器 感应电压试验 长时空载试验 过电流试验 拆解检查

2024

四川电力技术
四川省电机工程学会 四川电力试验研究院

四川电力技术

影响因子:0.347
ISSN:1003-6954
年,卷(期):2024.47(2)
  • 14