空分装置预冷系统冷冻水流量降低原因分析与防范

扫码查看
对某公司大型空分装置预冷系统冷冻水流量降低的原因进行分析,认为脱盐水硬度过大和含尘量高致使管道等结垢是预冷系统冷冻水流量降低的主要原因.针对性地采取一系列预防和处理措施后,冷冻水流量恢复至设计值,空冷塔出口压缩空气温度明显下降,减少了装置能耗,提高了生产效率,后续分子筛吸附系统负荷也有所降低,为空分装置的长周期、稳定运行提供了保障.
Analysis and Prevention of the Decrease in Chilled Water Flow Rate in the Pre Cooling System of an Air Separation Unit
An analysis is conducted on the reasons for the decrease in chilled water flow rate in the pre cooling system of a large air separation unit in a certain company.It is believed that the main reason for the decrease in chilled water flow rate in the pre cooling system is the excessive hardness and high dust content of the desalinated water,which leads to pipeline scaling.After taking a series of targeted preventive and treatment measures,the chilled water flow rate was restored to the design value,and the compressed air temperature at the outlet of the air cooling tower significantly decreased,reducing energy consumption and improving production efficiency.The subsequent load of the molecular sieve adsorption system was also reduced,providing a guarantee for the long-term and stable operation of the air separation unit.

air separation unitpre cooling systemwater cooling towerfrozen waterlow temperature scalingcause analysispreventive measures

郭厅、胡平

展开 >

河南能源集团贵州黔希化工有限责任公司,贵州黔西,551500

空分装置 预冷系统 水冷塔 冷冻水 低温结垢 原因分析 防范措施