山东电力高等专科学校学报2024,Vol.27Issue(6) :21-26.

500 kV变压器冷却系统寄生回路的分析及处理

Analysis and Treatment of Parasitic Circuit in Cooling System of a 500 kV Transformer

任志勇 张天旭 贾肖肖 宁欣
山东电力高等专科学校学报2024,Vol.27Issue(6) :21-26.

500 kV变压器冷却系统寄生回路的分析及处理

Analysis and Treatment of Parasitic Circuit in Cooling System of a 500 kV Transformer

任志勇 1张天旭 1贾肖肖 1宁欣1
扫码查看

作者信息

  • 1. 国网天津高压公司,天津 300232
  • 折叠

摘要

针对某500 kV强迫油循环风冷变压器在冷却器运行方式切换过程中出现的备用冷却器误启动故障,在分析备用冷却器启动控制回路原理的基础上,结合冷却系统现场检查情况,确定了故障原因,即在冷却器运行方式切换过程中,其控制回路中存在因时间继电器配合不当而产生的寄生回路,导致备用冷却器启动控制继电器动作.最后提出了在备用冷却器启动回路中设置切换开关的改进措施,为类似冷却系统故障的处理提供参考.

Abstract

In allusion to a fault of mistaken startup of the standby cooler during the process of switching the operation mode of the coolers of a 500 kV forced oil-circulated air-cooled transformer,based on the analysis of the principle of the startup control cir-cuit of the standby cooler,combining with the on-site inspection of the cooling system,the cause of the fault is determined,i.e.dur-ing the process of switching the operation mode of the coolers,the parasitic circuit in the control circuit due to the improper coordi-nation of time relays causes the startup control relay of the standby cooler to act.Finally,the improvement measure of setting trans-fer switch in the startup circuit of standby cooler is proposed,wihic provides reference for the treatment of similar cooling system faults.

关键词

变压器/冷却系统/寄生回路/时间继电器

Key words

transformer/cooling system/parasitic circuit/time relay

引用本文复制引用

出版年

2024
山东电力高等专科学校学报
山东电力高等专科学校

山东电力高等专科学校学报

影响因子:0.284
ISSN:1008-3162
段落导航相关论文