首页|电力变压器离线局部放电测量试验中的容升现象分析

电力变压器离线局部放电测量试验中的容升现象分析

扫码查看
Analysis of capacitive voltage rise during off-line partial discharge tests on power transformers
Partial discharge test on a transformer is carried out according to the items in IEC 60. During the test, unproved measuring system is calibrated by proved system at a voltage no less than 50% the rated testing voltage. The result is then extrapolated linearly, leading to an error related to the distribution of stray capacitance, which varies with the testing frequency, especially to large transformers. In this paper a factor, named the capacitive rise fact, is introduced to assess the rise. The factor can be adjusted to some extent by changing the reactance that is connected to the LV side of the testing circuit to lower the capacity of the power source. However, the factor changes when the voltage divider on the high voltage side is removed after the voltage ratio has been calculated, and a great error is resulted under unfavorable conditions.

transformer, stray capacitance, partial discharge, test.

王烜、曹晓珑、李云阁、刘英

展开 >

State Key Laboratory of Electrical Insulation for Power Equipment, Xi'an Jiaotong University, Xi'an 710049, P. R. China

High Voltage Department, China Electric Power Research Institute, Beijing 100085, P. R. China

transformer, stray capacitance, partial discharge, test.

2007

上海大学学报(英文版)
上海大学

上海大学学报(英文版)

影响因子:0.196
ISSN:1007-6417
年,卷(期):2007.11(5)