上海地铁某车站空调系统高效制冷机房改造实测分析

扫码查看
地铁车站空调系统高效技术是当前轨道交通节能降碳的主要手段,针对上海某地铁车站制冷机房高效化改造的具体情况、改造效果、能效提升进行了详细的分析和研究.改造选择了磁悬浮冷水机组,应用了变频技术来优化水泵的运行,改造后空调季制冷机房平均能效比达到5.16,年节电量约为30万kWh,节能效果显著.通过对制冷机房运行数据进行对比分析得知,负载率的优化对冷水机组能效具有直接而显著的影响,通过调整冷机出水温度和优化水泵变频策略,能进一步提高制冷机房的能效,为地铁车站制冷机房高效化改造和能效提升提供参考和帮助.
Experimental Analysis of Renovation of High-Efficiency Refrigeration Room for Air Conditioning System at a Station in Shanghai Subway
The high-efficiency technology of air conditioning system in subway stations is currently the main means of energy saving and carbon reduction in rail transit.A detailed analysis and study were conducted on the specific situation,transformation effect,and energy efficiency improvement of the high-efficiency transformation of the refrigeration room in a subway station in Shanghai.The magnetic suspension chiller was selected for the renovation,and the variable frequency technology was applied to optimize the operation of the water pump.After the renovation,the average energy efficiency ratio of the air conditioning season refrigeration room reached 5.16,and the annual power saving was about 300,000 kWh,which had significant energy saving effect.Through comparative analysis of the operat-ing data of the refrigeration room,it was found that optimization of the load rate had a direct and signifi-cant impact on the energy efficiency of the chiller.By adjusting the chiller outlet temperature and opti-mizing the variable frequency strategy of the water pump,the energy efficiency of the refrigeration room could be further improved,providing reference and assistance for the high-efficiency renovation and energy efficiency improvement of the refrigeration room in subway stations.

Subway StationHigh-Efficiency Machine RoomEnergy Efficiency RatioLoad RateWa-ter Outlet Temperature

宋洁、郑懿、张万毅

展开 >

上海申通地铁集团有限公司

同济大学

地铁站 高效机房 能效比 负载率 出水温度

上海市科委"科技创新行动计划"科技支撑碳达峰碳中和专项项目

22dz1208100

2024

上海节能
上海市节能协会,上海市节能监察中心

上海节能

影响因子:0.163
ISSN:
年,卷(期):2024.(1)
  • 4