石油化工设计2024,Vol.41Issue(1) :25-29.DOI:10.3969/j.issn.1005-8168.2024.01.006

常减压装置电脱盐罐安全阀泄放方案讨论及定压的确定

DISCUSSION ON RELIEF SCHEME OF SAFETY VALVE OF ELECTRIC DESALTER IN CDU/VDU AND THE DE-TERMINATION OF SET PRESSURE

党宇 昌兴文 张楚欣 刘统华 张泽忠 宋磊明
石油化工设计2024,Vol.41Issue(1) :25-29.DOI:10.3969/j.issn.1005-8168.2024.01.006

常减压装置电脱盐罐安全阀泄放方案讨论及定压的确定

DISCUSSION ON RELIEF SCHEME OF SAFETY VALVE OF ELECTRIC DESALTER IN CDU/VDU AND THE DE-TERMINATION OF SET PRESSURE

党宇 1昌兴文 1张楚欣 1刘统华 1张泽忠 1宋磊明1
扫码查看

作者信息

  • 1. 中石油华东设计院有限公司,山东青岛 266071
  • 折叠

摘要

传统的常减压装置电脱盐罐安全阀的安装位置通常无法满足安全泄放的要求,优化的安装位置为靠近闪蒸塔或初馏塔闪蒸段的平台或构架.事故工况下,安全阀出口泄放介质直接排往闪蒸塔或初馏塔,避免了安全阀出口管道因存在袋型或安全阀本身处于低点而影响自流排放的问题.因安全阀和电脱盐罐之间距离较远,不能满足标准API 520 中关于安全阀入口管道压降应小于安全阀定压的3%的要求,因此该条件下安全阀定压不能直接等同于电脱罐的设计压力,需扣除电脱罐出口与安全阀入口之间的静压差及流动阻力降.采用Aspen Plus软件中的 Safety Analysis模块,结合三维模型,将电脱罐出口与安全阀入口之间的阀门、管段和管件的数量和规格等关键信息输入,可以准确模拟流动阻力降,同时计算出电脱罐出口与安全阀入口之间的静压差,从而为安全阀定压设定提供依据.

Abstract

The traditional installation position of safety valve of electric desalter in CDU/VDU usually cannot meet the requirements of safe discharge.The optimized installation position is the platform or framework close to flash tower or the flash section of primary tower.Under accident conditions,the medium discharged from safety valve is directly sent to the flash tower or primary tower,so that the gravity flow discharge from the outlet piping of safety valve will not be affected by the pocket in pipe or the low position of the safety valve itself.Due to the long distance between the safety valve and the electric desalter,the requirement in API 520 that the pressure drop in the inlet piping of safety valve shall be less than 3%of the set pressure of safety valve cannot be met.Therefore,the set pressure of safety valve cannot be directly equivalent to the design pressure of electric desalter under this condition,and the static pressure difference and flow resistance drop between the outlet of electric desalter and the inlet of safety valve need to be deducted.This article uses the Safety Analysis module of Aspen Plus to input the key information such as the number and specification of valves,pipe sections and pipe fittings between the outlet of electric desalter and the inlet of safety valve combined with 3D model,so as to accurately simulate the flow resistance drop and calculate the static pressure difference between the outlet of desalter and the inlet of safety valve,providing a theoretical basis for determining the set pressure of safety valve.

关键词

常减压/电脱盐/安全阀/安装位置/定压

Key words

atmospheric&vacuum distillation/electric de-salting/safety valve/installation position/set pressure