首页|地铁站低压供配电线路连锁故障自动检测方法

地铁站低压供配电线路连锁故障自动检测方法

扫码查看
鉴于地铁站供配电线路布线复杂、交叉连接众多,为降低故障检测难度,针对其中可能存在的短路、接地故障、过载等多种故障类型,设计一种地铁站低压供配电线路连锁故障自动检测方法.通过故障分析,预判线路断开后出现连锁过载效应的线路的电压特征,根据电压特征变化判定连锁故障的起始环节.构建自动检测方法,在起始环节范围检测供配电线路连锁故障零序电压峭度,实现连锁故障高效检测.对比实验结果表明:该方法能准确检测故障发生时的电压波动情况,证明了所设计方法的有效性,且自动检测精准度更高,能够应用于实际运营中.
An Automated Detection Method for Cascading Faults in Low Voltage Power Distribution Lines of Subway Stations
Given the complex wiring and numerous cross-connections in subway station power distribution lines,a cascading fault automatic detection method for low voltage power distribution lines in subway stations is proposed to reduce fault detection difficulty.The method addresses various fault types that may occur in such lines,including short circuits,ground faults,and overloads.Through fault analysis,the voltage characteristics of lines that are likely to experience cascading overload effects after line disconnection are predicted.The cascading fault's initial stage is determined based on changes in voltage characteristics.The proposed automatic detection method detects the zero-sequence voltage steepness of cascading faults within the range of the initial stage,enabling efficient cascading fault detection.Experimental results demonstrate that the method can accurately detect voltage fluctuations during fault occurrence,proving the effectiveness of the proposed method.The method also exhibits higher automatic detection accuracy and can be applied in actual operation.

Subway stationLow voltagePower distribution lineCascading faultAutomated detection method

杨卫

展开 >

南通轨道交通集团有限公司运营分公司,南通 226000

地铁站 低压 供配电线路 连锁故障 自动检测方法

2024

微处理机
中国电子科技集团公司第四十七研究所

微处理机

影响因子:0.183
ISSN:1002-2279
年,卷(期):2024.45(3)
  • 7