首页|Harmonic Transfer Function Based Single-input Single-output Impedance Modeling of LCC-HVDC Systems
Harmonic Transfer Function Based Single-input Single-output Impedance Modeling of LCC-HVDC Systems
扫码查看
点击上方二维码区域,可以放大扫码查看
原文链接
万方数据
维普
This study presents a harmonic transfer function(HTF)based single-input single-output(SISO)impedance mod-eling method.The method converts an HTF from phase domain to sequence domain and then transforms it into an SISO imped-ance while preserving the frequency coupling information of dif-ferent sequences and different harmonics.Applications of this method to a line-commutated converter based high-voltage di-rect current(LCC-HVDC)system are presented.The results demonstrate the accuracy of the derived SISO impedance,and a truncation-order selection is suggested.The case study shows that the proposed method facilitates simpler impedance mea-surements and associated stability analysis.
Line-commutated converter based high-voltage direct current(LCC-HVDC)harmonic transfer function(HTF)single-input single-output(SISO)impedancefrequency coupling
Yang Wang、Fei Xia、Ying Wang、Xianyong Xiao
展开 >
College of Electrical Engineering,Sichuan University,Chengdu 610065,China