A级数据中心IT负载配电系统架构探讨
Discussion on the Architecture of IT Load Distribution System in A-Level Data Center
孙赟1
作者信息
- 1. 泽宇科技集团有限公司,福建厦门 361000
- 折叠
摘要
为设计人员提供A级数据中心IT负载配电系统架构选择依据,对配电系统架构形式、造价及用电可靠性进行讨论.在2N、DR、RR3个配电系统架构中,2N配电系统架构在造价上略高,但配电架构简单,后期运维存在较大优势,可靠性较高.综合考虑,推荐设计时优先选用2N配电系统架构.结果可供同类项目参考.
Abstract
This article aims to provide designers with a basis for selecting the architecture of A-level data center IT load distribution systems.Through discussions on the form,cost,and reliability of the distribution system architecture,it is concluded that among the three distribution system architectures of 2N,DR,and RR,the 2N distribution system architecture has a slightly higher cost but a simpler distribution architecture,which has significant advantages in later operation and maintenance and higher reliability.Taking into account all factors,it is recommended to prioritize the use of the 2N distribution system architecture in design.
关键词
A级数据中心/IT负载/配电系统/2N/DR/RRKey words
class A data center/IT loads/power distribution systems/2N/DR/RR引用本文复制引用
出版年
2024