西南交通大学学报2024,Vol.59Issue(1) :62-69.DOI:10.3969/j.issn.0258-2724.20220306

高原铁路站房地板辐射系统的分区供暖效果

Partition Heating Performance of Radiant Floor System in Railway Stations on Plateau

郑嘉诚 余涛 雷波 陈辰 吕瑞欣
西南交通大学学报2024,Vol.59Issue(1) :62-69.DOI:10.3969/j.issn.0258-2724.20220306

高原铁路站房地板辐射系统的分区供暖效果

Partition Heating Performance of Radiant Floor System in Railway Stations on Plateau

郑嘉诚 1余涛 1雷波 1陈辰 2吕瑞欣1
扫码查看

作者信息

  • 1. 西南交通大学机械工程学院,四川成都 610031
  • 2. 成都市建筑设计研究院有限公司,四川成都 610041
  • 折叠

摘要

为了解决高原铁路站房部分区域在强太阳辐射的影响下出现过热、地板辐射供暖系统能耗浪费的问题,以某高原铁路车站为研究对象,根据站房内太阳照射情况对地板辐射系统提出了分区供暖方案;利用建筑能耗模拟软件Energyplus对该铁路站房进行模拟分析,对比了地板辐射系统分区前后站房内的热环境和系统供暖量.结果表明:地板辐射系统采用统一的设计及运行控制方案供暖时,站房内太阳直射影响区的平均操作温度在日间最高可达 27℃,与非直射影响区之间的温差超过 5℃;在地板辐射系统分区供暖时,直射影响区的平均操作温度最高为 26℃,室内温度分布更为均匀,局部过热现象得到缓解;在保证站房热舒适性的前提下,地板辐射系统的分区供暖方案能够使直射影响区整个供暖季的供暖量降低38.2%.

Abstract

In order to solve the local overheating and the energy waste of radiant floor heating systems in railway stations on the plateau with intensive solar radiation,a railway station on the plateau was studied,and a partition heating scheme of the radiant floor system was proposed according to the solar radiation distribution in the station.The building energy consumption simulation software,namely Energyplus was used to simulate the station,and both the indoor thermal environment and the heating capacity of the radiant floor system with or without the partition scheme were compared.Results show that when the radiant floor system adopts a unified design and operation control scheme for heating,the average operative temperature in the irradiated zone can reach up to 27℃ during the daytime,and the temperature difference with the unirradiated zone is more than 5℃.When the radiant floor system uses the partition heating scheme,the maximum operative temperature in the irradiated zone is 26℃.The indoor temperature distribution is more uniform,and the local overheating is alleviated.Under the premise of ensuring the thermal comfort of the station,the partition heating scheme of the radiant floor system can reduce the heating capacity in the irradiated zone during the heating season by 38.2%.

关键词

铁路站房/太阳辐射/地板辐射供暖/室内热环境/系统供暖量

Key words

railway station/solar radiation/radiant floor heating/indoor thermal environment/heating capacity of system

引用本文复制引用

基金项目

国家自然科学基金(51708453)

四川省自然科学基金(2022NSFSC1944)

出版年

2024
西南交通大学学报
西南交通大学

西南交通大学学报

CSTPCDCSCD北大核心
影响因子:0.973
ISSN:0258-2724
参考文献量4
段落导航相关论文