Application of the Bithoba Flowmeter in Steam Measurement
In the steam flow measurement technology renovation project,the Bitoba flowmeter was selected to replace the original ultrasonic flowmeter.During the negotiation of the technical agreement,it was requested that the con-densate tank be eliminated and that the measurement be carried out by installing it directly above the pipe.Improvements were made to the root valve by replacing the original needle valve with a straight through gate valve and eliminating instrument heating in the design.The usage results indicate that the transmitter is not affected by high temperature and its temperature is consistent with the ambient temperature.The flowmeter is sensitive and stable in measurement,and the improvement effect is significant.