水电厂测温热电阻在使用一段时间后存在引线断线问题,通过检查和分析,判断其主要的原因是引线的幅度过大过小、材料不耐磨损、根部无保护和直径太细等,为此针对引线断线问题提出解决办法,采用一种铠装型引线直角弯头式热电阻,从而提高测温系统的稳定性,保证机组可靠运行.
Application and Research of a Armored Lead Square Elbow Thermal Resistance
The thermal resistance for temperature measurement in hydropower plants has a problem of wire breakage after being used for a period of time.Through inspection and analysis,it is determined that the main reasons are the amplitude of lead wire being too large or too small,the material not being wear-resistant,the root not being protected,and the diameter being too thin.This paper proposes a solution to improve the stability of the temperature measurement system and ensure the reliable operation of the unit by using an armored lead square elbow thermal resistance.

thermal resistancelead wire breakagelead amplitudetemperature measurement system