云南水力发电2024,Vol.40Issue(6) :1-2,6.DOI:10.3969/j.issn.1006-3951.2024.06.001

一种铠装型引线直角弯头式的热电阻的应用与研究

Application and Research of a Armored Lead Square Elbow Thermal Resistance

刘继永 李辉 余浩 罗黎 王俊
云南水力发电2024,Vol.40Issue(6) :1-2,6.DOI:10.3969/j.issn.1006-3951.2024.06.001

一种铠装型引线直角弯头式的热电阻的应用与研究

Application and Research of a Armored Lead Square Elbow Thermal Resistance

刘继永 1李辉 1余浩 1罗黎 1王俊1
扫码查看

作者信息

  • 1. 华电云南发电有限公司绿水河发电厂,云南 个旧 661014
  • 折叠

摘要

水电厂测温热电阻在使用一段时间后存在引线断线问题,通过检查和分析,判断其主要的原因是引线的幅度过大过小、材料不耐磨损、根部无保护和直径太细等,为此针对引线断线问题提出解决办法,采用一种铠装型引线直角弯头式热电阻,从而提高测温系统的稳定性,保证机组可靠运行.

Abstract

The thermal resistance for temperature measurement in hydropower plants has a problem of wire breakage after being used for a period of time.Through inspection and analysis,it is determined that the main reasons are the amplitude of lead wire being too large or too small,the material not being wear-resistant,the root not being protected,and the diameter being too thin.This paper proposes a solution to improve the stability of the temperature measurement system and ensure the reliable operation of the unit by using an armored lead square elbow thermal resistance.

关键词

热电阻/引线断线/引线幅度/测温系统

Key words

thermal resistance/lead wire breakage/lead amplitude/temperature measurement system