首页|Insulation Design Rule for a Spacer in SF6/N2-filled DC Gas Insulated Apparatus
Insulation Design Rule for a Spacer in SF6/N2-filled DC Gas Insulated Apparatus
扫码查看
点击上方二维码区域,可以放大扫码查看
原文链接
国家科技期刊平台
NETL
NSTL
万方数据
A recurring challenge of a DC SF6/N2-filled GIS/GIL apparatus is the charge accumulation at DC stress.The conventional design rules and knowledge of AC spacers may not be applicable for this new type of apparatus.A novel design rule is proposed considering the effect of accumulated charge on the threshold of electric field strength being resistant to the superposed voltage.A surface charge accumulation simulation model is introduced,and the key parameters in the simulation model are measured.In addition,an experimental platform for a 100 kV spacer flashover test is established.Spacer flashover tests under superimposed voltage with opposing polarities are carried out,and the withstanding voltage of the spacer is obtained.Finally,based on the proposed model,the threshold of the surface electric field strength(tangential component)on the DC spacer in SF6/N2 mixed gases is discussed.For a reliable insulation design of a DC GIS/GIL apparatus filled with 0.7 MPa SF6/N2,the threshold of surface electric field strength on the DC spacer is 12 kV/mm.The insulation design rule can be referenced in the design of a high-voltage DC SF6/N2-filled GIS/GIL apparatus.
Charge accumulationDC spacerflashover voltageSF6/N2threshold of surface electric field strength
Hongyang Zhou、Meng Zhang、Guoming Ma、Cong Wang、Youping Tu、Chengrong Li
展开 >
State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources and the Beijing Key Laboratory of High Voltage and EMC,North China Electric Power University,Beijing 102206,China
国家重点基础研究发展计划(973计划)Young Elite Scientists Sponsorship Program by CAST中央高校基本科研业务费专项