首页|Control Scheme of Spread Frequency Band for High Power Impedance Measuring Converter with Chirp Signal Injection
Control Scheme of Spread Frequency Band for High Power Impedance Measuring Converter with Chirp Signal Injection
扫码查看
点击上方二维码区域,可以放大扫码查看
原文链接
维普
万方数据
Impedance measurement is an effective solution for evaluating stability of a power system with high penetration of renewable sources.In this paper,the impedance measurement is achieved by a typical high-power impedance measuring converter(HPIM-converter)with chirp signal injection.The modulation saturation phenomenon of the HPIM-converter is revealed,and the frequency sweep boundary is analyzed in detail.To expand the rated frequency range of the HPIM-converter,a spread frequency band control scheme based on an over-modulation technique is proposed in this paper.The proposed control method enlarges the rated frequency band and can inject a disturbance voltage into the system under test with consistent amplitude in the rated frequency band.Also,a smooth transition strategy between linear modulation mode and over-modulation mode is proposed for suppressing signal fluctuation.Finally,the effectiveness of the proposed method is verified by simulation tests.
High-power impedance measurement deviceover-modulation techniquesmooth transition strategyspread frequency band
Wenli Yang、Junpeng Ma、Ruiting Sun、Shunliang Wang、Tianqi Liu
展开 >
College of Electrical Engineering,Sichuan University,Chengdu 610065,China