Troubleshooting and Resolution of Communication Faults in the YC-NTPS01 Intelligent Electric Energy Meter within the Framework of a Novel Power System Technology and Application Platform
The smart electricity meter is a crucial component of the power system,and its data acquisition function is vital for achieving intelligent and automated management of the system.This paper addresses the issue of data collection failure in DTZ1621 three-phase four-wire smart meters caused by communication faults within the new power system technology and application platform YC-NTPS01.It conducts a thorough examination of potential faults at both the hardware level of the communication system and the software layer,ultimately determining that the root cause of the communication failure is a change in the smart meter's communication address or meter number.After modifying the electricity meter's communication address in the power monitoring system software,the information from the DTZ1621 three-phase four-wire smart meter can be collected correctly.
abnormal communication of power metercommunication protocol of multifunction power metertroubleshooting