首页|变频冷水机组在轨道交通的应用能效分析

变频冷水机组在轨道交通的应用能效分析

扫码查看
地铁车站的人流量密集,舒适度要求高,是人们生活中极为重要的公共建筑。本文以深圳地铁12号线的新安公园站、左炮台站、福永站3个站点的空调系统为研究对象,从DeST的负荷模拟、机组性能曲线、运行的实测数据等方面对串联逆流超磁螺杆机组、永磁同步变频螺杆机组、永磁同步变频离心机组、机房和系统进行能效分析。结果表明,应用串联逆流技术的超磁螺杆机组能效较高,5-11月份其主机COP、EERs、TCOP分别达到8。52,7。10,4。05。
Operational Energy Efficiency Analysis of Variable Frequency Chillers for Underground Railway
Metro stations have a dense flow of people and high comfort requirements,and are extremely important public buildings in people's lives.This paper took the air conditioning systems of Xin'angongyuan Station,Zuopaotai Station and Fuyong Station of Shenzhen Metro Line 12 as the research objects,and analyzed the energy efficiency of super-magnetic screw units using series counter current technology,permanent magnet synchronous frequency conversion screw units,permanent magnet synchronous frequency conversion centrifuge units,machine rooms and systems from the aspects of DeST load simulation,unit performance curve and operation measured data.The results show that the energy efficiency of the ultra magnetic screw unit using series counter current technology is high,and the COP of its main engine,EERs,and TCOP are 8.52,7.10,and 4.05 respectively from May to November.

Underground Railway StationSeries Counter CurrentEnergy EfficiencyOperational TestEnergy Saving

刘舸争、李宏波、王珩、于德涌

展开 >

深圳市地铁集团有限公司,深圳,518026

珠海格力电器股份有限公司,珠海,519070

地铁站 串联逆流 能效 运行实测 节能

2024

制冷
广东省制冷学会,福建省制冷学会,河南省制冷学会,云南省制冷学会,广西区制冷学会

制冷

影响因子:0.432
ISSN:1005-9180
年,卷(期):2024.43(3)