扫码查看
本文对河北尚义抽水蓄能电站的通风洞兼安全洞、交通洞在永久期运营期间平均空气温度、相对湿度、空气焓值等参数的变化进行了数值模拟预测研究。计算结果表明室外新风在进入地下建筑之前温度和相对湿度发生了较大的变化。夏季通风洞兼安全洞末端的空气温度分别达到13。6℃,室外新风通过洞室壁面后夏季温降为14。6℃。夏季交通洞末端温度接近深层地温,夏季温降为18 ℃。因此通风洞兼安全洞、交通洞围护结构对室外新风温度的调控作用不可忽视。夏季通风洞兼安全洞、交通洞末端的相对湿度达到了 100%。两个洞室末端夏季相对湿度都达到了饱和,说明需要添加除湿或辅助热源设施,以缓解相对湿度过高对地下厂房造成的不利影响。
Research on the Air Temperature and Humidity Transfer Law in the Ventilation Corridor of the Underground Powerhouse of Pumped Storage Power Station in Summer
This study conducts numerical simulation research on the changes in parameters such as average air temperature,relative humidity,and air enthalpy during permanent operation of the ventilation tunnel,safety tunnel,and traffic tunnel of Hebei Shangyi Pumped Storage Power Station.The calculation results indicate that outdoor fresh air undergoes significant changes in temperature and relative humidity before entering underground buildings.The air temperatures at the ends of the ventilation and safety tunnels in summer reach 13.6 ℃,respectively.After outdoor fresh air passes through the walls of the tunnel,the summer temperature drops to 14.6 ℃.The temperature at the end of the traffic tunnel in summer is close to the deep ground temperature,and the temperature drop in summer is 18 ℃.Therefore,the control effect of the ventilation tunnel,safety tunnel,and traffic tunnel enclosure structure on outdoor fresh air temperature cannot be ignored.The relative humidity at the end of the ventilation tunnel,safety tunnel,and traffic tunnel reached 100%in summer.The relative humidity at the ends of both chambers reached saturation in summer,indicating the need to add dehumidification or auxiliary heat source facilities to alleviate the adverse effects of high relative humidity on the underground powerhouse.

Pumped Storage Power StationVentilation GalleryUnderground BuildingsTransmission Law

潘亚、李阳、沈雄

展开 >

中国电建集团北京勘测设计研究院有限公司,北京,100024

天津大学,天津,300072

抽水蓄能电站 通风廊道 地下建筑 传递规律

2024

制冷
广东省制冷学会,福建省制冷学会,河南省制冷学会,云南省制冷学会,广西区制冷学会

制冷

影响因子:0.432
ISSN:1005-9180
年,卷(期):2024.43(3)