Design Summary of Variable Air Volume Air Conditioning System for Office Buildings in Shenzhen Area
Based on engineering examples,the design process of variable air volume air conditioning systems is introduced in detail,and the design cases and operation debugging feedback of variable air volume air conditioning systems in office buildings in Shenzhen are analyzed.Suggestions for the selection of combined air cabinets for variable air volume air conditioning systems are obtained.The indoor cooling index should not be less than 120W/m2,including fresh air cooling index should not be less than 150W/m2,the external static pressure should not be less than 600pa,and the air supply index per unit air conditioning area should be 25-30m3/h/m2.The research results meet the current work needs and provide reference opinions for similar projects in the industry.
Variable Air Volume Air Conditioning SystemEnthalpy Humidity ChartSuper High Rise Office BuildingEngineering ExampleVariable Air Volume Terminal BOX