首页|无风管自净型排风柜吸附效率实测分析和研究

无风管自净型排风柜吸附效率实测分析和研究

扫码查看
对配置三组并联式吸附过滤器的无风管自净型排风柜进行吸附效率实测,得到结论,实验条件下柜内热源数量会很大程度影响其过滤效率。相同蒸发浓度,柜内三个热源较单一热源散发污染物时吸附效率高出30~50%;柜内中心单一热源散发污染物时,中间过滤器率先被穿透,整组过滤器的有效利用率低,过滤器的额定吸附量较小。提出了现行的JG/T 385-2012有必要针对配置多组吸附过滤器的无管自净型排风柜明确更具体的测试方法和评价指标。
Experimental Analysis and Research on Adsorption Efficiency of Ductless Self-filtration Vented Enclosure
The adsorption efficiency of a ductless self-filtration vented enclosure equipped with three sets of parallel adsorption filters was measured,and the conclusion was drawn that the number of heat sources inside the cabinet will greatly affect its filtration efficiency under experimental conditions.At the same evaporation concentration,the adsorption efficiency of three heat sources inside the cabinet is 30%to 50%higher than that of a single heat source when emitting pollutants;When a single heat source emits pollutants from the center of the cabinet,the intermediate filter is the first to be penetrated,resulting in a low effective utilization rate of the entire set of filters and a smaller rated adsorption capacity of the filters.It has been proposed that the current JG/T 385-2012 requires more specific testing methods and evaluation indicators for ductless self-filtration vented enclosures equipped with multiple sets of adsorption filters.

Ductless Self-cleaning Exhaust CabinetAdsorption FilterAdsorption Filtration EfficiencyHeat SourceRated Adsorption Capacity

付茜、刘东、张俊伟、郭裕铎

展开 >

同济大学

无风管自净型排风柜 吸附过滤器 吸附过滤效率 热源 额定吸附量

2024

制冷
广东省制冷学会,福建省制冷学会,河南省制冷学会,云南省制冷学会,广西区制冷学会

制冷

影响因子:0.432
ISSN:1005-9180
年,卷(期):2024.43(6)