Application of indirect evaporative cooling technology to energy-saving reconstruction for data center
Indirect evaporative cooling technology,high-temperature chilled water technology with large temperature difference and dynamic ice storage technology are ap-plied to one old data center for energy-saving reconstruction,and the operation tests are conducted.The results show that after the energy-saving reconstruction,the PUE of data center changes from 2.00 to 1.25,and the power consumption of the air-conditioning sys-tem in the data center is reduced by 75%.