Large temperature difference water storage air conditioning system based on double head series counterflow
The working principle,dehumidification mode and system characteristics of large temperature difference water storage air conditioning system based on double head series reverse current are introduced.The main engine part adopts double head series counterflow,the end part is a group of empty units,using the form of two-stage surface cooling,heat and humidity combined treatment,and at the same time adopts large tem-perature difference energy storage,which solves the problem of excessive cold storage vol-ume of water storage and cooling system.Finally,the system is applied to a certain exhi-bition hall,which reduces the equipment capacity,the cold storage density is large,the volume of the cold storage tank is greatly reduced,and the low-cost electricity storage at night is used to greatly reduce the operating costs.
double cold sourcetwo-stage table coolinglarge temperature differenceseries countercurrent