制冷与空调2024,Vol.24Issue(6) :43-46,54.DOI:10.3969/j.issn.1009-8402.2024.06.007

基于大数据的多联式空调(热泵)机组待机情况分析

Standby situation analysis on multi-connected air-condition(heat pump)units based on big data

陈宗衍 牟桂贤 刁作清 申伟刚
制冷与空调2024,Vol.24Issue(6) :43-46,54.DOI:10.3969/j.issn.1009-8402.2024.06.007

基于大数据的多联式空调(热泵)机组待机情况分析

Standby situation analysis on multi-connected air-condition(heat pump)units based on big data

陈宗衍 1牟桂贤 1刁作清 1申伟刚1
扫码查看

作者信息

  • 1. 格力电器股份有限公司
  • 折叠

摘要

基于蜂窝通信模块获取分布于全国的 22.6 万套多联式空调(热泵)机组(简称"多联机")的运行情况,按照建筑气候区划、使用环境等分析多联机的待机情况.研究结果显示:多联机的平均待机率达69.2%,其中家用多联机平均待机率为 74.3%,商用多联机平均待机率为 56.9%,家用多联机平均待机率比商用多联机高 17.4%;每台多联机平均每年待机耗电量达 91.0 kW·h.

Abstract

Based on the operation status of 226 000 sets of multi-connected air-condi-tion(heat pump)units in China obtained by the cellular communication module,the standby situations of multi-connected air-condition(heat pump)units are analyzed accord-ing to the building climate demarcation and the operation environment.The research re-sults show that the average standby rate of multi-connected air-condition(heat pump)u-nits is 69.2%,of which the average standby rate of the residential multi-connected air-con-dition(heat pump)units is 74.3%,and the average standby rate of the commercial multi-connected air-condition(heat pump)units is 56.9%,thus the former standby rate is 17.4%higher than the latter.The average power consumption of each multi-connected air-condition(heat pump)units is 91.0 kW·h every year.

关键词

多联式空调(热泵)机组/耗电量/待机/节能

Key words

multi-connected air-condition(heat pump)units/power consumption/standby/energy-saving

引用本文复制引用

出版年

2024
制冷与空调
中国制冷空调工业协会 中国科学技术交流中心

制冷与空调

影响因子:0.331
ISSN:1009-8402
参考文献量12
段落导航相关论文