首页|某数据机房低负载率下冷却系统水泵变频节能研究

某数据机房低负载率下冷却系统水泵变频节能研究

扫码查看
随着数据中心行业的不断发展,我国在用数据中心机架规模不断增长,截至 2021 年底已达 520 万架.与此同时,数据中心的耗电量不断增长,2020 年我国数据中心耗电量突破 2 000 亿kWh.实际运营过程中,数据中心上架率远低于设计水平,造成低负载率运行能耗居高不下.对数据中心冷却系统进行变频水泵改造可有效解决低负载率运行冷却系统能源浪费问题.文章利用 TRNSYS仿真平台对数据中心全水冷却系统建立能耗模型,并基于模型对水泵变频改造进行分析研究.结果表明,在机房负载率为 10%~25%运行情况下,水泵变频改造后,数据中心全水制冷系统泵耗降低 150 kW~168 kW 不等,一年可节约电能约143 万 kWh(折合 176t标煤);离心式冷水机组能效水平 COP 值从 6.2 提高至 7.9;机房 PUE 最高可降低0.36,变频水泵改造节能效果明显.
Research on the transformation of variable frequency pump of cooling system under low load rate in a data center
TRNSYS simulation platform is used to establish the energy consumption model of the cooling system in the data center.Based on the model,the frequency conver-sion transformation of the water pump is analyzed and studied.The results show that un-der the low load operation with the load rate of 10%~25%in the IDC,the pump energy consumption of the refrigeration system in the IDC is reduced by 150 kW~168 kW.The COP of chiller is increased from 6.2 to 8.0.Using variable frequency pump can effectively reduce PUE,up to 0.36.

internet data centerlow load ratevariable frequency pumpTRNSYSPUE