Comparative study on air conditioning system scheme of Shaoguan data center project
Based on the background of the three development policies of"new infra-structure","double carbon"and"East count and west count",this paper makes a com-parative analysis of the air conditioning system scheme selection of the newly built data center in Shaoguan area.In order to meet the requirements of energy consumption index of PUE≤1.25,WUE≤1.4 L/kWh for newly built data centers in Shaoguan area,this paper compared three new air conditioning system schemes using indirect evaporative cooling air conditioning unit(AHU),indirect evaporative cooling tower and evaporative cooling heat pipe multi-link system.According to the above three air conditioning system schemes from the basic performance,PUE value,WUE value,economy,out of the box rate,operation and maintenance and customer acceptance are analyzed,to provide the basis and ideas for the selection of new data center air conditioning system schemes in Shaoguan area.
data centerair-conditioning systemPUEWUEeconomic analysis