首页|数据中心空调系统能效测算及影响因素分析

数据中心空调系统能效测算及影响因素分析

扫码查看
对北京地区某数据中心空调系统能效进行全年动态模拟计算,分析系统实际冷负荷率及冷水机组能效对系统能效的影响.结果表明:采用冷水机组A时,空调系统在负荷率100%下全年平均设计能效比为9.61,远低于负荷率70%时全年平均设计能效比;在负荷率70%下,与采用冷水机组A相比,采用与其具有相同制冷量但不同COP的冷水机组B时,空调系统全年平均设计能效比提升0.54.
Energy efficiency assessment and influencing factors analysis on air-conditioning system for data centers
A year-round dynamic simulation is conducted on the energy efficiency of the air-conditioning system of a data center in Beijing.The influence of actual cooling load ratio and energy efficiency of the water chiller on the system energy efficiency is analy-zed.The results show that when utilizing water chiller A,the air-conditioning system ob-tains an annual average design energy efficiency ratio (EER)of 9.61 at 100% load ratio,which is much lower than the EER achieved at 70% load ratio.At 70% load ratio,the use of water chiller B,which has the same cooling capacity but a different coefficient of per-formance (COP),results in an increase of 0.54 in the annual average design EER of the air-conditioning system,compared with using water chiller A.

data centerair-conditioning systemnatural coolingenergy efficiency

许宗金、邹思、罗灿、杨雪斌

展开 >

广东申菱环境系统股份有限公司

数据中心 空调系统 自然冷却 能效

2024

制冷与空调
中国制冷空调工业协会 中国科学技术交流中心

制冷与空调

影响因子:0.331
ISSN:1009-8402
年,卷(期):2024.24(11)