制冷与空调2024,Vol.24Issue(11) :22-28.DOI:10.3969/j.issn.1009-8402.2024.11.004

数据中心空调系统能效测算及影响因素分析

Energy efficiency assessment and influencing factors analysis on air-conditioning system for data centers

许宗金 邹思 罗灿 杨雪斌
制冷与空调2024,Vol.24Issue(11) :22-28.DOI:10.3969/j.issn.1009-8402.2024.11.004

数据中心空调系统能效测算及影响因素分析

Energy efficiency assessment and influencing factors analysis on air-conditioning system for data centers

许宗金 1邹思 1罗灿 1杨雪斌1
扫码查看

作者信息

  • 1. 广东申菱环境系统股份有限公司
  • 折叠

摘要

对北京地区某数据中心空调系统能效进行全年动态模拟计算,分析系统实际冷负荷率及冷水机组能效对系统能效的影响.结果表明:采用冷水机组A时,空调系统在负荷率100%下全年平均设计能效比为9.61,远低于负荷率70%时全年平均设计能效比;在负荷率70%下,与采用冷水机组A相比,采用与其具有相同制冷量但不同COP的冷水机组B时,空调系统全年平均设计能效比提升0.54.

Abstract

A year-round dynamic simulation is conducted on the energy efficiency of the air-conditioning system of a data center in Beijing.The influence of actual cooling load ratio and energy efficiency of the water chiller on the system energy efficiency is analy-zed.The results show that when utilizing water chiller A,the air-conditioning system ob-tains an annual average design energy efficiency ratio (EER)of 9.61 at 100% load ratio,which is much lower than the EER achieved at 70% load ratio.At 70% load ratio,the use of water chiller B,which has the same cooling capacity but a different coefficient of per-formance (COP),results in an increase of 0.54 in the annual average design EER of the air-conditioning system,compared with using water chiller A.

关键词

数据中心/空调系统/自然冷却/能效

Key words

data center/air-conditioning system/natural cooling/energy efficiency