In order to improve the risk prevention and control capability of oil storage security protection in data centers and the ability of designers to respond to changes in external conditions.Taking the safety protection design analysis of daily oil storage room in a data center project as an example,making an analysis of fire and explosion risks was conducted in relevant terms and requirements,including the type of diesel used,oil storage environment,and fuel supply process.The conclusion drawn from the analysis is that the daily oil storage room of the project should be designed for electrical equipment in accordance with the zone 2 standard for explosive gas environments.At the end,a complete electrical safety protection technical scheme for the project is provided,aiming to provide reference experience for similar projects in oil storage safety protection.
关键词
爆炸危险环境/严寒地区/日用储油间/电力装置设计/可燃气体探测报警系统
Key words
explosive gas environment/severe cold regions/daily oil storage room/power device design/combustible gas detection and alarm system