首页|Pitting corrosion of copper tubes for fire sprinkler system
Pitting corrosion of copper tubes for fire sprinkler system
扫码查看
点击上方二维码区域,可以放大扫码查看
原文链接
NSTL
Elsevier
Failure analyses with 10 leaked and 10 non-leaked Cu tubes for a fire sprinkler system were conducted to understand the cause of pitting corrosion. Water analysis revealed that the water in the leaked tubes was more corrosive than that in the non-leaked tubes. Surface analysis revealed that the leakage due to the pitting corrosion occurred with carbonaceous residue and deposits in the presence of trapped air in the tube. Furthermore, the chloric residue in the as-received Cu tube induced localized corrosion on the Cu.
ACu BEPMAXRDPolarizationEIS CPitting corrosionION CONCENTRATIONCHLORIDESTEELSULFATEFAILUREWATER3-BENZOTRIAZOLEIMPEDANCEALUMINUMALLOYS