Applied thermal engineering2022,Vol.2046.DOI:10.1016/j.applthermaleng.2021.117945

Importance of long-term ground-loop temperature variation in performance optimization of Ground Source Heat Pump system

Wang F. Chen S. Chen C. Kolditz O. Shao H. Zhang Y. Cai W.
Applied thermal engineering2022,Vol.2046.DOI:10.1016/j.applthermaleng.2021.117945

Importance of long-term ground-loop temperature variation in performance optimization of Ground Source Heat Pump system

Wang F. 1Chen S. 2Chen C. 2Kolditz O. 2Shao H. 2Zhang Y. 3Cai W.1
扫码查看

作者信息

  • 1. School of Human Settlements and Civil Engineering Xi'an Jiaotong University
  • 2. Helmholtz Centre for Environmental Research-UFZ
  • 3. Key Laboratory of Coal Resources Exploration and Comprehensive Utilisation Ministry of Natural Resources
  • 折叠

Abstract

In a recent article published in this journal, a series of design optimization was executed for a ground source heat pump system. The optimization was conducted based on a COPall index, which considers both the hydraulic loss on the buried pipe network, as well as the soil thermal balance over a one-year period. In that article, it was concluded that a borehole spacing of 4m is the optimal value. In this short communication, the comprehensive COPall index is re-evaluated with the same system setup with both the TRNSYS and OpenGeoSys-TESPy software, but over a 20-year period. The results show that the borehole heat exchanger array with a spacing of 4m will suffer severe heat accumulation over a 20-year operation. This causes the soil temperature to rise by 5.68°C, along with a decrease of COPall from 4.59 to 4.18. Due to the smaller increase of ground-loop temperature and lower electricity consumption from heat pumps, a larger spacing of 6m will bring better COPall value over the long term, and thus should be recommended. The extended numerical study in this work suggests that when evaluating the performance of a ground source heat pump system, different time duration will lead to different results. Therefore, the variation of long-term ground-loop temperature needs to be quantitatively evaluated in advance, and the system optimization is recommended to be conducted over the entire life cycle of the system.

Key words

Borehole heat exchanger array/Ground-loop temperature/Shallow geothermal energy utilization/Soil thermal balance/System optimization

引用本文复制引用

出版年

2022
Applied thermal engineering

Applied thermal engineering

EISCI
ISSN:1359-4311
被引量8
参考文献量29
段落导航相关论文