Applied thermal engineering2022,Vol.21513.DOI:10.1016/j.applthermaleng.2022.118940

Numerical and experimental investigation of desiccant cooling system using metal organic framework materials

Andrew N. Aziz Saad Mahmoud Raya Al-Dadah Mohamed A. Ismail Mohammed K. Al Mesfer
Applied thermal engineering2022,Vol.21513.DOI:10.1016/j.applthermaleng.2022.118940

Numerical and experimental investigation of desiccant cooling system using metal organic framework materials

Andrew N. Aziz 1Saad Mahmoud 1Raya Al-Dadah 1Mohamed A. Ismail 2Mohammed K. Al Mesfer2
扫码查看

作者信息

  • 1. School of Engineering, University of Birmingham
  • 2. Department of Chemical Engineering, College of Engineering, King Khalid University
  • 折叠

Abstract

Evaporative cooling consumes fraction of the electricity required by the vapour compression refrigeration system but is only effective in dry weather conditions. A promising method for controlling the incoming air humidity is to use a desiccant wheel before the evaporative cooler. Currently, most desiccant cooling systems employ conventional materials like silica gel or zeolites which have low water uptake. Metal Organic Framework (MOF) materials are new class of meso-porous material with high water adsorption capabilities (~1.5 kg/kgads). Using numerical modelling and experimental testing, this paper investigates the use of four MOF materials namely CPO27(NI), MIL100(Fe), MIL-101(Cr), Aluminium Fumarate and silica gel on the performance of a stationary desiccant heat exchanger (honeycomb Aluminium structure coated with MOF desiccant material) in terms of the Coefficient of performance (COP) and moisture removal rate. Numerical results showed that Aluminium fumarate produced the highest COP of 0.65 with water removal rate of 12.65 g/kg dry air and MIL-101(Cr) produced the highest moisture removal of 15.99 g/kg dry air but with COP of 0.44 compared to silica gel and other MOF materials used. Experimental tests were carried out using honeycomb structure coated with Aluminium fumarate as the stationary desiccant wheel and results were compared to numerical modelling showing good agreement with maximum deviation of 13%. Experimental and modelling results showed that the rate of moisture removal increases with the increase of air inlet humidity and with the decrease of incoming air speed. Also, results showed that the highest moisture removal occur after the first 2 min from starting the dehumidification process highlighting the advantage of using MOF materials.

Key words

Desiccant modelling/MoF material/Metal organic framework/Desiccant wheel and experimental/Investigation

引用本文复制引用

出版年

2022
Applied thermal engineering

Applied thermal engineering

EISCI
ISSN:1359-4311
被引量6
参考文献量33
段落导航相关论文