首页|Flammable performance and experimental evaluation of a new blend as R404A lower-GWP alternative

Flammable performance and experimental evaluation of a new blend as R404A lower-GWP alternative

扫码查看
Current alternatives to R404A are either refrigerants with higher global warming potentials (GWP) from 1200 to 2000 or mildly flammable refrigerants with a charge limit of 1.2 kg. Therefore, nonflammable alternatives to R404A with lower GWP values need to be developed. In this study, a new non-flammable refrigerant blend, named RTJU-Z (GWP of 794), has been proposed to directly replace R404A in a cold storage system with no modification. The flammability and thermodynamic performance of RTJU-Z were studied experimentally. The results show that RTJU-Z couldn't be ignited successfully and had a higher coefficient of performance (COP) value than that of R404A by 2.15%-5.71% at different cold storage temperatures. The optimal charge of RTJU-Z for the experimental system was 11.76% lower than that of R404A. The refrigeration capacity of RTJU-Z was about the same as that of R404A at the cold storage temperature from -20 °C to 10 °C. It is concluded that RTJU-Z can be directly used as a non-flammable alternative to R404A in a cold storage system with no modification.

AlternativeFlammabilityLow GWPR404ARTJU-ZThermodynamic performance

Zhang L.、Yang Z.、Zhai R.、Lv Z.、Zhang Y.、Deng Q.

展开 >

Key Laboratory of Efficient Utilization of Low and Medium Grade Energy Ministry of Education School of Mechanical Engineering Tianjin University

2022

International Journal of Refrigeration

International Journal of Refrigeration

EISCI
ISSN:0140-7007
年,卷(期):2022.135
  • 4
  • 26