Applied thermal engineering2022,Vol.20716.DOI:10.1016/j.applthermaleng.2022.118148

Investigation on the cooling performance of a buoyancy driven earth-air heat exchanger system and the impact on indoor thermal environment

Long T. Li Y. Qiao Z. Lu J. Zheng D. Ye K. Huang S. Li W. Liu S.
Applied thermal engineering2022,Vol.20716.DOI:10.1016/j.applthermaleng.2022.118148

Investigation on the cooling performance of a buoyancy driven earth-air heat exchanger system and the impact on indoor thermal environment

Long T. 1Li Y. 1Qiao Z. 1Lu J. 1Zheng D. 1Ye K. 1Huang S. 1Li W. 2Liu S.3
扫码查看

作者信息

  • 1. School of Civil Engineering Chongqing University
  • 2. Department of Building Science School of Architecture Tsinghua University
  • 3. School of Mechanical Engineering Beijing Institute of Technology
  • 折叠

Abstract

The feasibility and cooling performance of a pure buoyancy-driven earth-air heat exchanger system (B-EAHE) with the assistance of combined effect of solar chimney and thermal mass were verified and revealed by a full-scale experimental study. The experimental results showed that the EAHE pipe diameter plays an important role in the system performance, and the airflow rates reach peak values of approximately 252 m3/h and 166 m3/h for the EAHE pipes with diameters of 0.3 m and 0.2 m, respectively. The air temperature differences between the inlet and outlet of the EAHE were approximately 12.5 °C and 13.0 °C in maximum, and 4.8 °C and 4.78 °C in average for the EAHE pipes with diameters of 0.2 and 0.3 m. In addition, the amplitude of indoor air temperature was further attenuated under the regulation of the B-EAHE system. The air temperature inside reference chamber varies from 28.3 to 35.1 °C, while the air temperature inside test chamber with 0.3 m diameter pipe ranges from 28.5 to 30 °C, which is approximately 2 °C lower than that for test chamber with 0.2 m diameter pipe. Moreover, higher energy saving potential is justified by the 0.3 m diameter pipe with peak cooling capacity of 1179 W compared with the 0.2 m diameter pipe with peak cooling capacity of 629 W. It is concluded that the B-EAHE system is able to achieve 24 h periodically fluctuating natural ventilation and passive cooling, and to improve the indoor thermal environment greatly in hot summer conditions.

Key words

Buoyancy force/Earth-air heat exchanger/Indoor thermal environment/Solar chimney/Thermal mass