首页|Experimental investigation of a new combined refrigeration system

Experimental investigation of a new combined refrigeration system

扫码查看
In this paper, experimental study has been performed to investigate the performance of a new combined cooling system (CCS) included indirect evaporative cooler and 4-bed solar adsorption cooling system. Solar adsorption cooling system acted as pre-cooling for the CCS. in this study, two mass flow rates passing from evaporator of 0.1 and 0.15 kg s?1, and also three volumetric air flow rates passing from indirect evaporative cooler of 700, 850 and 1000 m3 h?1, were investigated. Results were shown that, the highest average efficiency was 104% and obtained for minimum of mass flow passing from solar adsorption cooling system (0.1 kg s?1) and minimum of volumetric air passing from indirect evaporative coolind system (700 m3 h?1). Also, the average efficiency of combined cooling was in the range of 84–104%.

Combined refrigeration systemContinuous solar adsorption cooling systemEnhancement performanceIndirect evaporative cooling system

Goudarzi K.、Jalil E.、Mousavi M.R.

展开 >

Department of Mechanical Engineering Yasouj University

2022

International Journal of Refrigeration

International Journal of Refrigeration

EISCI
ISSN:0140-7007
年,卷(期):2022.134