首页|Failure analysis of platen superheater tube, water wall tube, and sealpot plate: A case study from electricity power plant in indonesia
Failure analysis of platen superheater tube, water wall tube, and sealpot plate: A case study from electricity power plant in indonesia
扫码查看
点击上方二维码区域,可以放大扫码查看
原文链接
NSTL
Elsevier
? 2022 Elsevier LtdFailure analysis of the platen superheater tube, water wall tube, and sealpot plate were investigated in the present study. To examine the causes of failure, various techniques, including visual examination, chemical composition test using Optical Emission Spectrometry (OES), fracture surface examination using Scanning Electron Microscope (SEM), tensile test, hardness test, and metallography test were carried out. Samples average thickness were 6.46 mm, 6.23 mm, and 9.29 mm, respectively. The chemical composition of the platen superheater tube, water wall tube, and sealpot plate material samples was not conforming to the standard material. The eroded tube surface contributed to the failure mechanism that caused by escaping steam in high velocity which leading to another leakage. This escaping steam also damages the adjacent surface by 'steam cutting' mode and erosion in both platen superheater tube and water wall tube.