Simulation Study of a Longitudinally Induced Ventilation System in Tall and Large Factory Buildings of the Covered Metro Vehicle Base
This study proposes a solution involving the use of a longitudinally induced ventilation system to solve ventilation challenges in factory buildings within a covered metro vehicle base,where natural ventilation is impractical and traditional horizontal ventilation systems are difficult to implement.We first created a three-dimensional model for the longitudinally induced ventilation system,analyzed the impacts of the induced jet fan installation spacing and height on the airflow within the factory building based on numerical simulation results,and validated the proposed system against actual engineering conditions.The results indicate that the best overall and workstation ventilation effects can be achieved with installation spacings of 20 and 25 m,respectively,along with heights of 8 and 6 m,respectively,for the induced jet fans inside the factory building.The field tests agreed well with the simulation results.This study provides a theoretical basis for the application of longitudinal ventilation systems in engineering applications.
rail transitfactory buildings of the coveredvehicle basetall and large factory buildingsnumerical simulationlongitudinal induced ventilation system