电网技术2024,Vol.48Issue(2) :904-912,中插95-中插98.DOI:10.13335/j.1000-3673.pst.2022.2509

选择型直流输电控制系统实用机电暂态建模与参数校核方法

Practical Electromechanical Transient Modeling and Parameter Calibration for HVDC Control System Based on Selection

吴国旸 宋新立 李霞 戴汉扬 彭忠 张艳浩 李慧 肖龙
电网技术2024,Vol.48Issue(2) :904-912,中插95-中插98.DOI:10.13335/j.1000-3673.pst.2022.2509

选择型直流输电控制系统实用机电暂态建模与参数校核方法

Practical Electromechanical Transient Modeling and Parameter Calibration for HVDC Control System Based on Selection

吴国旸 1宋新立 1李霞 1戴汉扬 1彭忠 2张艳浩 2李慧 3肖龙2
扫码查看

作者信息

  • 1. 中国电力科学研究院有限公司,北京市 海淀区 100192
  • 2. 许继电气股份有限公司,河南省 许昌市 461000
  • 3. 北京信息科技大学自动化学院,北京市 海淀区 100192
  • 折叠

摘要

目前,国内高压直流输电技术分为两类:一是基于ABB、南瑞技术路线的限幅型直流,二是基于 SIEMENS、许继技术路线的选择型直流.前者已有成熟机电暂态仿真模型,而后者尚缺乏深入研究,通常以限幅型模型近似代替,仿真结果与实际尚有一定差距,难以满足电力系统安全稳定计算的需求.该文在总结直流输电系统机电暂态建模原则的基础上,建立了选择型直流的精细化模型;利用轨迹灵敏度筛选出需校核参数,提出了基于实测数据的关键参数校核方法;并在中国通用的电力系统暂态稳定程序(power system department power tools-swing transient,PSD-ST)中开发实现,最后利用厂家电磁暂态仿真结果验证了模型的正确性.该文成果可改善直流控制系统模型缺失、仿真能力受限问题,有效提升机电暂态仿真程序的仿真精度.

Abstract

At present,there are two HVDC technical routes of HVDC control system in China,one is the HVDC control system based on limit by the ABB,NARI,and the other is the HVDC control system based on selection by the SIEMENS,XJ.The former has got a mature electromechanical transient simulation model,while modeling of the latter still lacks in-depth researches.It is usually replaced by a HVDC control system model based on limit.There is still a great difference between the simulation results and the actual characteristics,which cannot meet the needs of the power system security and stability calculation.This paper summarizes the electromechanical transient modeling principle of the HVDC transmission systems,establishes a refined model of the HVDC control systems based on selection;The paper proposes a key parameter screen and verification method based on the measured data and the trajectory sensitivity.This new modeling method is implemented in the general power system simulation program PSD-ST in China.Finally,the correctness of the model is verified by the manufacturer electromagnetic transient simulation results.The results of this paper will solve the problem of the lack of HVDC control system model,and effectively improve the simulation accuracy of the electromechanical transient simulation program.

关键词

选择型直流/机电暂态/建模/参数校核

Key words

HVDC control system based on selection/electromechanical transient/modeling/parameter calibration

引用本文复制引用

基金项目

国家电网公司科技项目()

北京市自然科学基金项目(3232045)

出版年

2024
电网技术
国家电网公司

电网技术

CSTPCD北大核心
影响因子:2.821
ISSN:1000-3673
参考文献量14
段落导航相关论文