电网技术2024,Vol.48Issue(7) :2967-2976,中插94-中插95.DOI:10.13335/j.1000-3673.pst.2023.1135

含逆变型分布式电源外电网的短路计算等值及其影响因素分析

Short-circuit Calculation Equivalent of External Power Grid Including Inverter Interfaced Distributed Generator and Analysis of Influencing Factors

谢德兴 肖仕武
电网技术2024,Vol.48Issue(7) :2967-2976,中插94-中插95.DOI:10.13335/j.1000-3673.pst.2023.1135

含逆变型分布式电源外电网的短路计算等值及其影响因素分析

Short-circuit Calculation Equivalent of External Power Grid Including Inverter Interfaced Distributed Generator and Analysis of Influencing Factors

谢德兴 1肖仕武1
扫码查看

作者信息

  • 1. 新能源电力系统国家重点实验室(华北电力大学),北京市 昌平区 102206
  • 折叠

摘要

大量逆变型分布式电源接入会对电网短路电流计算及电网等值产生影响.该文提出了含逆变型分布式电源外电网的多端口戴维南等值方法,分析了等值参数的影响因素.首先,基于多端口电网络理论推导了外电网等值多端口的戴维南等值电路模型和参数表达式,分布式电源对等值电路的影响主要体现在开路等效电压.其次,根据开路电压计算公式,分析了分布式电源对开路等效电压的影响因素和规律.电网故障期间分布式电源可等效为压控电流源,其输出电流受独立电压源、等值端口电压及分布式电源低穿控制策略等的影响.然后,分析了等值端口电压、分布式电源容量、独立交流电源强弱对等效开路电压的影响规律,得到了等效开路电压随端口电压、分布式电源容量和外部电源内阻抗的变化曲线.通过IEEE33节点电网和某220kV高压电网仿真验证了等值方法和影响因素分析的正确性.

Abstract

Integrating many inverter-interfaced distributed generators(IIDG)will impact the power system's calculation of short-circuit current and grid equivalence.This paper proposes a multi-port Thevenin equivalent method for an external grid with a distributed generator,and the influencing factors of equivalent parameters are analyzed.Firstly,the Thevenin equivalent circuit model and parameter expression are derived based on the theory of multi-port electrical networks.The influence of distributed generators on equivalent circuits is mainly reflected in the open-circuit equivalent voltage.Secondly,according to the formula of open circuit voltage calculation,distributed generators'influence factors and rules on open circuit equivalent voltage are analyzed.The distributed generator can be equivalent to the voltage-controlled current source,and its output current is affected by the independent voltage source,the equivalent port voltage,and the low pass control strategy of the distributed generator.Then,the effect of equivalent port voltage,the capacity of the distributed generator,and the strength of independent AC power supply on equivalent open circuit voltage is analyzed,and the variation curve of equivalent open circuit voltage with port voltage,the capacity of the distributed generator,and internal impedance of external power supply is obtained.The simulation results of the IEEE33-node power grid and 220kV high-voltage power grid verify the correctness of the equivalence method and the analysis of influencing factors.

关键词

多端口戴维南等值/逆变型分布式电源/短路电流计算

Key words

multi-port Thevenin equivalent/inverter interfaced distributed generator/short circuit current calculation

引用本文复制引用

基金项目

国网冀北公司项目(52018K230001)

出版年

2024
电网技术
国家电网公司

电网技术

CSTPCDCSCD北大核心
影响因子:2.821
ISSN:1000-3673
参考文献量21
段落导航相关论文