电网技术2024,Vol.48Issue(10) :4195-4205,中插67-中插69.DOI:10.13335/j.1000-3673.pst.2023.1683

考虑多热源协同互补的含先进绝热压缩空气储能系统容量配置方法

A Capacity Allocation Method for Advanced Adiabatic Compressed Air Energy Storage Systems Considering the Synergistic Complementarity of Multiple Heat Sources

崔杨 于一凡 付小标 仲悟之 赵钰婷
电网技术2024,Vol.48Issue(10) :4195-4205,中插67-中插69.DOI:10.13335/j.1000-3673.pst.2023.1683

考虑多热源协同互补的含先进绝热压缩空气储能系统容量配置方法

A Capacity Allocation Method for Advanced Adiabatic Compressed Air Energy Storage Systems Considering the Synergistic Complementarity of Multiple Heat Sources

崔杨 1于一凡 1付小标 2仲悟之 3赵钰婷1
扫码查看

作者信息

  • 1. 现代电力系统仿真控制与绿色电能新技术教育部重点实验室(东北电力大学),吉林省 吉林市 132012
  • 2. 国网吉林省电力有限公司,吉林省长春市 130012
  • 3. 中国电力科学研究院有限公司,北京市海淀区 100192
  • 折叠

摘要

先进绝热压缩空气储能(advanced adiabatic compressed air energy storage,AA-CAES)具备天然的热电联供特性,能够有效缓解供热期出现的弃风问题.若能在规划阶段充分考虑运行需求,进而合理地配置储能容量,则能够在解决弃风问题的前提下,最大程度对燃煤机组进行清洁替代.为此,该文提出了多热源协同互补的AA-CAES系统容量配置模型.首先本模型在能量输入端引入电锅炉预热压缩机入口空气,以增大压缩机输气系数并提高机组产热量;其次在扩展热源端,通过太阳能反射镜场收集光热,以提高系统储热水平;并在计及储能系统各模块实际运行效率约束之余,以运行总成本最小为目标,计算储能容量配置最优解.再次,分析供热时长及环境温度等因素对投资成本回收年限的影响,并计算不同情况下本模型投资成本的回收年限,得出建设本模型可盈利的硬性条件;最后,基于东北某地区供热期及非供热期典型日负荷及气象数据在IEEE-39节点系统完成算例分析,验证所提模型有效性.

Abstract

Advanced adiabatic compressed air energy storage(AA-CAES)has natural cogeneration characteristics,which can effectively alleviate the problem of wind abandonment during the heating period.Suppose operational needs can be fully considered during the planning stage and energy storage capacity can be reasonably configured.In that case,it can maximize the clean replacement of coal-fired units while solving the problem of wind abandonment.This article proposes a capacity configuration model for AA-CAES systems with multiple heat sources that complement each other.Firstly,this model introduces an electric boiler to preheat the inlet air of the compressor at the energy input end to increase the compressor's gas transmission coefficient and the unit's heating capacity.Secondly,at the expansion heat source end,solar energy is collected through a reflective mirror field to improve the system's heat storage level And taking into account the actual operational efficiency constraints of each module of the energy storage system,to minimize the total operating cost,the optimal solution for energy storage capacity configuration is calculated.Once again,analyze the impact of factors such as the length of the heating period and environmental temperature on the investment cost recovery period and calculate the recovery period of the investment cost of this model under different circumstances to obtain the hard conditions for building this model to be profitable;Finally,based on typical daily loads and meteorological data during heating and non-heating periods in a certain region of Northeast China,a numerical analysis was completed in the IEEE-39 node system to verify the effectiveness of the proposed model.

关键词

供热期/先进绝热压缩空气储能/太阳能集热模块/容量配置/热电联产

Key words

heating supply period/advanced adiabatic compressed air energy storage/solar collector modules/capacity configuration/combined heat and power

引用本文复制引用

基金项目

国家自然科学基金项目(51777027)

出版年

2024
电网技术
国家电网公司

电网技术

CSTPCD北大核心
影响因子:2.821
ISSN:1000-3673
参考文献量21
段落导航相关论文