首页|基于改进阈值函数的直埋供热管网检漏研究

基于改进阈值函数的直埋供热管网检漏研究

扫码查看
为提高声波法直埋热水供热管网泄漏应用的定位精度,在分析各种小波法阈值函数适用性的基础上,提出了改进阈值函数降噪方法,该方法理论上能够克服软阈值函数的恒定偏差和硬阈值函数信号振荡的缺点,设置调节参数,提升降噪能力,保留小于阈值点区域信号,避免有效信号丢失.在大型直埋热水循环管网中进行泄漏测试实验,研究表明采用本方法进行声波法直埋供热管道泄漏检测,可实现泄漏定位误差在±1 m内,定位精度可达0.11%~3.49%,最后选择北京市供热系统中实际工程案例,采用本方法进行声波法泄漏检测,泄漏定位误差为0.37%~0.66%,定位精度提升.
Research on the leak detection of directly buried heating pipe network by an improved threshold function
To improve the positioning accuracy of the leakage application of the direct buried hot water heating pipe network by acoustic method,based on the analysis of the applicability of various wavelet threshold functions,an improved threshold function noise reduction method is proposed. This method can theoretically overcome the constant deviation of the soft threshold function and the shortcomings of the hard threshold function signal oscillation. Through setting adjustment parameters,improving the noise reduction ability,and retaining the signal of the region less than the threshold point to avoid effective signal loss. The experiment was carried out in a large direct buried hot water circulation pipe network. The research showed that the leakage positioning error was within±1 m and the positioning accuracy reached 0.11%~3.49%. Finally,the acoustic leakage detection method was adopted in a practical engineering case of a Beijing heating system. The leakage location error is 0.37%~0.66%,and the positioning accuracy has efficiently is improved.

threshold functiondirectly buried heating pipelinesacoustic methodleakage detectionorientation

徐自强、李成、穆连波、王随林、刘建军

展开 >

北京建筑大学环境与能源工程学院 北京 100044

北京市热力集团有限公司 北京 100028

改进阈值函数 直埋供热管道 声波法 泄漏检测 定位

北京市热力集团合作项目北京学者计划项目北京市教育委员会科研计划项目

KY1910072015NO.022KM202310016006

2024

电子测量技术
北京无线电技术研究所

电子测量技术

CSTPCD北大核心
影响因子:1.166
ISSN:1002-7300
年,卷(期):2024.47(6)
  • 23