首页|绿色办公建筑主被动式设计实际运行效果评价——以广东某办公楼为例

绿色办公建筑主被动式设计实际运行效果评价——以广东某办公楼为例

Evaluation of Actual Operation Effect of Active and Passive Design of Green Office Building:A case study of an office building in Guangdong

扫码查看
广东某办公楼基于气候特征,利用自身资源条件,因地制宜地集成了多种被动式设计,即将建筑朝向优化、金属穿孔板遮阳罩结合形体自遮阳以及中庭、天井、下沉庭院设计强化自然通风、自然采光等被动技术结合,同时辅以温湿度独立控制、湖水源热泵空调系统的主动式技术,以期最大化地降低建筑能耗.建筑运行后,依据实际运行及检测数据,有针对性地对室内外风环境、热湿环境、光环境及空气品质进行分析,验证了被动式、主动式节能技术应用效果良好,项目最终能耗较《民用建筑能耗标准》(GB/T 51161-2016)引导值降低了 27.4%.但同时结合运行效果,提示今后设计可以在以下方面改进:考虑用能习惯设计供暖热源;适当减少半室外地下车库排风设备数量;温湿度独立控制空调系统在运行时,湿热天气需要提前开启空调除湿功能以防止结露.
Based on climatic characteristics,an office building in Guangdong integrates various passive designs according to local conditions,optimizing The building orientation,combining metal perforated plate sunshade with self-shading,atrium patio sinking courtyard design,strengthening the natural ventilation,natural lighting and other passive technologies,while supplemented by active technology of temperature and humidity independent control and lake water source heat pump air conditioning system,in order to maximize the reduction of building energy consumption.According to the actual operation and test data,the indoor and outdoor wind,heat,humidity and air quality are verified.The application effect of passive and active energy-saving technology is good.The final energy consumption of the project is 27.4%lower than that of"Civil Building Energy Consumption Standard"(GB/T 51161-2016).Combined with the operation effect,it is suggested that the design can be improved in the aspects including the consideration of the energy consumption habit,design of the heating source,reduction on the number of exhaust equipment in semi-outdoor underground garages appropriately,as well as starting the air conditioner dehumidification in advance to prevent dew condensation in hot and humid weather when the temperature and humidity independent control air conditioning system is running.

green buildingspassive energy-saving technologyactive energy-saving technologymeasured resultsoperational energy consumption

葛鑫

展开 >

清华大学建筑设计研究院有限公司,北京 100084

绿色建筑 被动式节能技术 主动式节能技术 实测效果 运行能耗

2024

建筑节能(中英文)
中国建筑东北设计研究院有限公司

建筑节能(中英文)

CSTPCD
影响因子:0.695
ISSN:2096-9422