建筑节能(中英文)2024,Vol.52Issue(8) :98-102.DOI:10.3969/j.issn.2096-9422.2024.08.015

气密性分区测试方法在大体量建筑中的应用

Application of Air Tightness Partition Test Method in Large-scale Buildings

杜争 袁涛 李泽奇 王营 黄雨函 游晓静 樊晓
建筑节能(中英文)2024,Vol.52Issue(8) :98-102.DOI:10.3969/j.issn.2096-9422.2024.08.015

气密性分区测试方法在大体量建筑中的应用

Application of Air Tightness Partition Test Method in Large-scale Buildings

杜争 1袁涛 1李泽奇 1王营 1黄雨函 1游晓静 1樊晓2
扫码查看

作者信息

  • 1. 建科环能科技有限公司,北京 100013
  • 2. 河南兴华电力设计有限公司,郑州 450001
  • 折叠

摘要

我国建筑能源消耗量大,气密性是影响建筑能耗的重要因素.为研究大体量建筑整体气密性测试的方法,以我国寒冷地区某新建大体量建筑为例,从围护结构封堵措施、区域划分、漏气量限值计算及测点布置等方面详细介绍了大体量建筑气密性测试的过程和要点,提出利用分区测试的方法对大体量建筑进行气密性能测试,并得出被测建筑的整体气密性实测值.结果表明:采用分区测试的方法进行大体量建筑气密性测试可减少大体量建筑测试时受到设备的限制及外界环境因素的影响.为大体量建筑进行气密性能测试、完善建筑施工、缩短测试周期、性能评价方面提供参考与建议.

Abstract

The energy consumption of building is relatively high in China. The air tightness is an important factor affecting the energy consumption of building. In order to study the method of overall air tightness test of large-scale buildings,taking a new large-scale building in a cold area of China as an example,the process and key points of the air tightness test of large-scale buildings were introduced in detail from the aspects of enclosure structure plugging measures,regional division,calculation of air leakage limits,and layout of measuring points. Put forward to use partition testing method to test the air tightness of large buildings and obtain the actual measured value of the overall airtightness of the tested building. The test results indicate that using partition testing method for air tightness testing of large buildings can reduce the limitations of equipment and the influence of external environmental factors. Provide reference and suggestions for conducting air tightness performance testing,improving building construction,shortening testing cycles,and performance evaluation for large-scale buildings.

关键词

大体量建筑/气密性能/分区测试/缩短测试周期

Key words

large-scale buildings/air tightness/partition testing/shorten testing cycles

引用本文复制引用

出版年

2024
建筑节能(中英文)
中国建筑东北设计研究院有限公司

建筑节能(中英文)

CSTPCD
影响因子:0.695
ISSN:2096-9422
参考文献量5
段落导航相关论文