采用智能减压阀降低北海某片区管网漏损率
Measures to Reduce the Leakage Rate of Water Supply in a Certain Area of Beihai City
陈康伟1
作者信息
- 1. 北海市供水有限责任公司,广西 北海 536000
- 折叠
摘要
北海市供水有限责任公司针对银滩回建区爆管频繁,用户投诉增多,近几年漏损率特别高的问题,采取主动压力管理措施,通过安装智能减压阀,分时段分级控压.经过 4 个月的调试运行,最不利点平均压力由 0.31 Mpa下降至 0.23 Mpa,漏损率下降 22.1%,达到降低漏损率和爆管率,并产生良好经济效益的目的.
Abstract
Beihai Water Supply Co.,Ltd.had taken proactive pressure management measures to address the frequent pipe bursts,increased user complaints,and particularly high leakage rates in the Yintan Reconstruction Zone in recent years.By installing intelligent pressure reducing valves and controlling pressure in stages and stages.After 4 months of debugging and operation,the average pressure at the most unfavorable point decreased from 0.31 Mpa to 0.23 Mpa,and the leakage rate decreased by 22.1%,achieving the goal of reducing leakage rate and tube pipe burst rate,and generating good economic benefits.
关键词
漏损控制/爆管/压力管理/智能减压阀Key words
leakage control/pipe burst/Water pressure management/Intelligent pressure reducing valve引用本文复制引用
出版年
2024