Ground Source Heat Pump with Storage System of the Plant factory
In order to solve the problem of greenhouse gas and harmful gas polluting environment,which released by fossil fuels used to supply energy to plant factory,ground source heat pump with storage system is designed for the plant factory.More specifically,using groundwater source heat pump with storage system can transport part of the peak load in the day to the evening so as to use redundant power at night.On the basis of calculation results,the water source heat pump of heating capacity and refrigeration capacity are 799kw and 613kw respectively.Through the cooling and heating load of the plant factory,the quantity of pumping groundwater is 78.9 m3/h.In addition,the volume of heat and cool storage tanks are 400 m3 and 600 m3 respectively.The economic benefits and energy conservation and emissions reduction benefits of the ground source heat pump with storage system of the plant factory are analysed finally.
hot storagepeak load shiftinggroundwater source heat pumpplant factoryenergy supply system