首页|10 kV并联电容器谐振分析与对策研究

10 kV并联电容器谐振分析与对策研究

扫码查看
针对近期发生在云南电网某供电局的一起谐波放大事件,首先对电容器投切前后的实测谐波数据进行对比分析,验证了这是一次由于并联电容器接入后,与系统发生谐波谐振造成谐波电流放大的现象,然后通过仿真建模揭示了并联电容器对谐波电流放大的机理,最后基于谐波谐振理论提出了针对10 kV并联电容器谐波谐振的抑制措施.
Resonance Analysis and Countermeasure Research of 10 kV Shunt Capacitor
Aiming at a recent harmonic amplification event in a power supply bureau of Yunnan Power Grid,the measured harmonic data before and after capacitor switching were compared and analyzed to veri-fy that this is a phenomenon of harmonic current amplification caused by harmonic resonance with the sys-tem after the shunt capacitor is connected,and then the mechanism of harmonic current amplification by shunt capacitor was revealed through simulation modeling.Finally,based on the theory of harmonic reso-nance,the suppression measures for harmonic resonance of 10 kV shunt capacitors were proposed.

shunt capacitorharmonic resonanceharmonic amplificationseries reactance

孔垂锐、詹兴旺、文虎标、周航、李文娟、彭朝柱

展开 >

云南电网有限责任公司曲靖马龙供电局,云南曲靖 655000

昆明理工大学电力工程学院,云南 昆明 650500

并联电容器 谐波谐振 谐波放大 串抗率

云南电网公司科技项目

YNKJXM20220053

2024

机械与电子
中国机械工业联合会科技工作部 机械与电子杂志社

机械与电子

CSTPCD
影响因子:0.243
ISSN:1001-2257
年,卷(期):2024.42(10)