我国4.4.2类高等级病原微生物实验室运行现状及问题思考

扫码查看
本文分析了我国数十家已建成并投入使用的4.4.2类高等级病原微生物实验室设施运行现状,包括实验室总体建设概况、实验室核心工作间环境参数、气流组织形式和压力调节方式,以及实验室自控系统运行可靠性等.研究结果表明,我国4.4.2类实验室大多设计为2~4间核心工作间、1套独立空调通风系统的形式.核心工作间采用上送上排和上送下排气流组织的比例大致相同,大多采用定送风变排风的压力调节形式.在室内环境和系统可靠性方面,研究发现实验室存在换气次数普遍偏高、部分实验室对室外大气绝对压力过大现象.此外,个别实验室存在因送/排风机切换或空调系统开/关机产生过大负压导致围护结构开裂、防护区最外围房间发生绝对压力逆转、UPS设置等问题.本文还分析了常见的共性问题产生原因,并给出了改进建议,以期提升我国高等级病原微生物实验室建设和运行管理水平、确保实验室设施环境满足建成后的实际需求、保障运行管理安全高效.
Analysis of operational and common problems of high-level pathogenic microorganism laboratory facilities(Class 4.4.2)in China
To improve the construction and management standards of high-level pathogenic microorganism laboratories,ensure that the laboratory facility environment conforms to national standards and codes,serves the actual needs after completion,and operates safely and efficiently,the operating status of many completed and functional high-level pathogenic microorganism laboratory facilities(Class 4.4.2 in existing national standards of China,GB 19489-2008 Laboratories-General requirements for biosafety)was analyzed.This analysis included the overall construction of the laboratory,the environmental parameters of the main room,and the operation reliability of the laboratory air conditioning and automatic control system.The analysis results show that the protected areas of the investigated high-level pathogenic microorganism laboratories are usually designed with a layout of locker rooms(including shower rooms),protective clothing rooms,isolation corridors,buffer rooms,and main rooms.An independent air conditioning system supports two to four main rooms.Most of the cleanliness classifications are ISO 8,and a few others are ISO 7.The main room adopts the up-supply and up-exhaust or up-supply and down-exhaust air distribution.The pressure regulation modes of the main room mostly have constant supply and variable exhaust air volumes.Regarding the indoor environmental parameters,the analysis results show that all laboratories were in line with the relevant standards and codes.Additionally,the air exchange rate of the main rooms is mostly higher than the standard limit.Some main rooms have excessive outdoor atmospheric absolute pressure,so it was considered that the energy-saving potential can be further optimized,adjusted,and released.Regarding the reliability of the air conditioning and automatic control system,the laboratory fan interlock and working condition conversion,alarm,monitoring,communication,and power supply systems are functional.However,in some laboratories,a relative pressure reversal phenomenon of less than 1 min is observed between the main room and its buffer room during the switching and turning on/off the air supply/exhaust fan processes.The analysis also shows that some laboratories had problems,such as cracking of the enclosure structure and absolute pressure reversal in the outermost room of the laboratory containment area,due to the excessive negative pressure while switching the air supply/exhaust fan.The unreasonable design of the number and the location of the uninterrupted power supply sockets is a reason for the difficulty in maintaining the backup air supply and exhaust system forms.Additionally,design recommendations were proffered,considering the discussion on backup ventilation systems in high-level biosafety laboratories while drawing comparisons between the independent fan backup mode and the whole air conditioning unit backup mode.Finally,all the questions were analyzed,and suggestions for design and management improvement were proposed.

biosafetyhigh-level pathogenic microorganism laboratoryClass 4.4.2 laboratoryfacility environmentoperation situation

陈紫光、曹国庆、王荣、李沐洋、刘波波、高鹏、尹婧、王博雅、赵倩玉

展开 >

中国建筑科学研究院有限公司,北京 100013

中国合格评定国家认可中心,北京 100062

中国科学院武汉病毒研究所,武汉 430071

生物安全 高等级病原微生物实验室 4.4.2类实验室 设施环境 运行现状

中国建筑科学研究院有限公司基金

20220106330730007

2024

科学通报
中国科学院国家自然科学基金委员会

科学通报

CSTPCD北大核心
影响因子:1.269
ISSN:0023-074X
年,卷(期):2024.69(9)
  • 13