首页|一机一泵组合的冷却水泵工作区与变频运行分析

一机一泵组合的冷却水泵工作区与变频运行分析

扫码查看
根据深圳前海10号制冷站区域供冷系统,建立了 一机一泵组合的冷却水系统水力计算模型,包括共享的总管+冷却塔压降模型,以及各支路的压降模型.针对不同运行模式,得到了水泵工作区;结合水泵变频特性曲线,得到了每个水泵工作区不同流量对应的水泵运行频率范围,可用于水泵变频控制,简化水泵运行控制策略.本文提出的水泵工作区还可用于水泵选型,校核水泵在所有工况是否运行在高效区.
Analysis of cooling water pump working zone and variable frequency operation of one-pump-one-chiller combination
Based on Qianhai DCS Plant No.10 in Shenzhen,a hydraulic calculation model is developed for the one-pump-one-chiller combination cooling water systems considering the shared pressure drops of the shared main pipe and cooling towers,and the individual pressure drops of the pump branches.According to different operation modes,the pump working zones are obtained.Combined with the frequency conversion characteristic curve of the pump,the pump frequency operation zone is obtained corresponding to different flows in each pump working zone,which can be used for the frequency conversion control of the pump,and the pump operation control strategy is simplified.The pump working zone proposed in this paper can also be used for pump selection to check whether the pump is running in the high efficiency zone under all the operation conditions.

district cooling systemone-pump-one-chiller combinationhydraulic calculation modelpump working zonepump frequency operation zonepump selection

旷金国、王朝晖、罗曙光、陈盛阶、叶圳

展开 >

深圳市前海能源科技发展有限公司,深圳

区域供冷系统 一机一泵组合 水力计算模型 水泵工作区 水泵运行频率范围 水泵选型

2024

暖通空调
亚太建设科技信息研究院 中国建筑设计研究院 中国建筑学会暖通空调分会

暖通空调

CSTPCD
影响因子:0.711
ISSN:1002-8501
年,卷(期):2024.54(1)
  • 1