首页|考虑初始风速与机端故障稳态电压跌落程度的直驱风机故障响应特性分类及其判别方法研究

考虑初始风速与机端故障稳态电压跌落程度的直驱风机故障响应特性分类及其判别方法研究

扫码查看
对电力系统进行安全分析时,往往需要对各种预想场景进行仿真。随着风电的大量接入,对风电场提出适用于预想故障分析的等值建模方法变得十分重要,而根据风机故障后的动态特性对其进行分群则是等值建模的基础。各风机在故障后的动态响应特性不仅受其控制方式的影响,还受到运行风速和故障严重程度的影响,而一般情况下风机控制的响应速度较快,可以认为在故障持续期间风机能够运行至故障稳态。基于此,提出考虑初始风速及机端故障稳态电压跌落程度的风电机组故障响应特性分类及判别方法,以此作为风机分群的依据。首先针对永磁直驱风机(direct-driven permanent magnet synchronous generator,PMSG)故障过程中无功优先控制、故障恢复期间有功斜坡恢复的控制策略,分析其在不同风速条件下故障后所有可能的响应特性,将初始风速与故障稳态电压作为分类指标,从机理上找到直驱风机进入各类响应特性的边界条件;然后,提出利用预想故障信息的风机机端故障稳态电压计算方法,在此基础上提出适用于预想故障的直驱风机分群方法;最后,通过对风电场进行详细建模仿真,验证所提分群方法的正确性。
Study on Fault Response Characteristics Classification and Discriminant Method of PMSG Considering Initial Wind Speed and Drop Degree of Terminal Fault Steady-state Voltage
Security analysis of power systems often requires simulation of various expected scenarios.With massive integration of wind power,it is important to put forward an equivalent modeling method suitable for the anticipated fault for wind farms.Meanwhile,grouping wind turbines by their dynamic response characteristics is the basis of equivalent modeling.The dynamic response characteristics of each wind turbine after a fault are not only affected by the control mode,but also by the operating wind speed and the severity of the fault.In general,the control of wind turbines can work rapidly and run to fault steady state during the fault.For the above reasons,this paper proposes a classification and discrimination method for the fault response characteristics of wind turbines considering the initial wind speed and terminal fault steady-state voltage drop degree.First,for the control strategy of reactive power priority control during fault process and active power ramp recovery during fault recovery,all possible characteristics of wind turbines and the critical condition of all clusters can be found.Then,based on the anticipated fault,a fault steady-state voltage calculation method for each wind turbine in a wind farm is proposed.Further,a clustering method adapted to anticipated fault is proposed.Finally,the simulation analysis of a detailed wind farm model proves the correctness of the proposed method.

direct-driven permanent magnet synchronous generatoractive power responseramp recoveryanticipated faultclustering method

李东晟、沈沉、吴林林、程雪坤、杨艳晨

展开 >

清华大学电机工程与应用电子技术系,北京市 海淀区 100084

国网冀北电力科学研究院,北京市 西城区 100045

永磁直驱风机 有功响应 斜坡恢复 预想故障 分群方法

国家电网公司科技项目

4000-202214067A-1-1-ZN

2024

中国电机工程学报
中国电机工程学会

中国电机工程学报

CSTPCD北大核心
影响因子:2.712
ISSN:0258-8013
年,卷(期):2024.44(4)
  • 24