首页|基于电压迭代的直驱风电场短路电流计算方法

基于电压迭代的直驱风电场短路电流计算方法

A short-circuit current calculation method for direct-driven wind farms based on voltage iteration

扫码查看
风电场短路电流计算普遍采用等值模型,不计内部线路、变压器等因素,精度欠佳;而考虑上述因素的短路电流计算方法多采用电压电流同时迭代的方式,其收敛性难以直观验证.为此,提出了一种计及风电场内部结构参数的短路电流算法.首先,结合限幅作用下的D-PMSG(永磁直驱风电机组)电流特性与最大维度的风电场节点电压方程,构建了风电场短路电流计算模型;其次,利用诺顿等值消去未知电流参数,并结合工况变化确定修正的节点电压方程;最后,结合电压迭代,得出了基于修正模型和风电场特性的短路电流计算方法.仿真对比结果表明,所提方法具有较高的准确性以及更好的收敛性.
Short-circuit current calculations for wind farms typically employ equivalent models that neglect internal lines,transformers,and other critical factors,leading to reduced accuracy.Methods that account for these factors often rely on simultaneous voltage and current iteration,which complicates the intuitive verification of convergence.To address such issues,this paper proposes a short-circuit current calculation method that incorporates the internal structural parameters of wind farms.Based on the current characteristics of direct-driven permanent magnet synchro-nous generators(D-PMSG)under current-limiting conditions and the equations for the maximum node voltage of wind farm,a calculation model for short-circuit current in a wind farm is built.Then,Norton equivalence is applied to eliminate unknown current parameters,and the modified node voltage equation based on varying operating condi-tions is established.Finally,by implementing voltage iteration,a modified short-circuit current calculation method based on the modified model and the characteristics of the wind farm is obtained.Simulation comparisons demon-strate that the proposed method offers enhanced accuracy and improved convergence.

large-scale wind farmshort-circuit currentD-PMSGiterative calculationlimiting effect

骆尧涵、汤皓环、李金裕、侯山、薛安成

展开 >

国网江苏省电力有限公司宜兴市供电分公司,江苏 无锡 214200

新能源电力系统国家重点实验室(华北电力大学),北京 102206

广东电网有限责任公司广州供电局,广州 510620

国网河北省电力有限公司石家庄供电分公司,石家庄 050051

展开 >

大规模风电场 短路电流 永磁直驱风电机组 迭代计算 限幅作用

国家重点研发计划

2021YFB2401000

2024

浙江电力
浙江省电力学会 浙江省电力试验研究院

浙江电力

CSTPCD
影响因子:0.438
ISSN:1007-1881
年,卷(期):2024.43(10)