基于TRNSYS的季节性冰储冷与蒸发冷却耦合的空调系统能耗分析

扫码查看
针对现有空调系统能耗较高,以及蒸发冷却空调技术受室外环境影响制取冷风温度波动不稳定的问题,提出了一种季节性冰储冷与蒸发冷却耦合的空调系统,将冬天的冷量储存到夏天来用,辅助蒸发冷却技术制取冷风.并以榆林市的某数据中心为例,基于TRNSYS模拟软件对该系统建立了模型,分析冷量全年储存情况,验证了其在榆林地区冷量捕获和储存的可行性.对其全年运行能耗进行了模拟,得出数据中心PUE值全年稳定在1.1左右.将季节性冰储冷与蒸发冷却耦合空调系统与同等制冷量下机械制冷和蒸发冷却加机械制冷的空调系统能耗情况进行了节能对比,PUE分别降低了0.66和 0.13.
Energy Consumption Analysis of Air Conditioning System Coupled with Seasonal Ice Storage and Evaporative Cooling Based on TRNSYS
In response to the problems of high energy consumption of existing air conditioning systems and unstable temperature fluctuations of cold air produced by evaporative cooling air conditioning technology due to the outdoor environment,a seasonal ice storage and evaporative cooling coupled air conditioning system is proposed to store the cold in winter for use in summer and assist evaporative cooling technology to produce cold air.And a data center in Yulin city is taken as an example,and the system is modeled based on TRNSYS simulation software to analyze the cold storage throughout the year and verify its feasibility of cold capture and storage in Yulin area.Its annual operation energy consumption was simulated,and it was concluded that the data center PUE value was stable at about 1.1 throughout the year.The energy consumption of the coupled seasonal ice storage and evaporative cooling air conditioning system was compared with that of the mechanical cooling and evaporative cooling plus mechanical cooling air conditioning systems with the same cooling capacity,and the PUE was reduced by 0.66 and 0.13,respectively.

TRNSYSSeasonal ice storageEvaporative coolingPUE

闫泳橙、孙铁柱、王祺、马杰、孙欢

展开 >

西安工程大学城市规划与市政工程学院 西安 710048

TRNSYS 季节性冰储冷 蒸发冷却 PUE

2024

制冷与空调(四川)
四川省制冷学会 西南交通大学

制冷与空调(四川)

CSTPCD
影响因子:0.475
ISSN:1671-6612
年,卷(期):2024.38(1)
  • 17