首页|平疫结合社区通风系统设计及卫生通过风量平衡计算分析

平疫结合社区通风系统设计及卫生通过风量平衡计算分析

扫码查看
以河南省郑州市某平疫结合社区为例,介绍了平疫转换涉及的主要建筑功能布局和通风系统设计要求.根据风量平衡公式,计算并分析了在门窗缝隙为 0.004m,一脱防护服房间换气次数 20h-1条件下,卫生通过区相邻相通房间压差对通风量的影响.在穿防护服房间压力为 5Pa,更衣室房间压力为 10Pa,二脱防护服房间压力为-5Pa,一脱防护服房间压力为-25Pa时,各房间通风量最小,更衣室送风换气次数为 22.9h-1,穿防护服房间送风换气次数为3.4h-1,一脱防护服房间送风换气次数为 6.9h-1,二脱防护服房间排风换气次数为 4.2h-1.
The Analysis of Ventilation System Design and the Air Volume Balance Calculation of Hygiene Passing Through with the Combination of Normal Time with Epidemic Period in a Community
Taking the example of a community with combination of normal time with epidemic period in Zhengzhou,Henan Province,the main building function layout and ventilation system design requirements with epidemic conversion are introduced.According to the equation of air quantity balance,the influence of pressure difference between adjacent rooms in the hygiene passing through on air quantity was analyzed under the conditions that the door and window gap were 0.004m and the air change rate was 20h-1 in the first undressed room.When the pressure in the protective clothing dressing room is 5Pa,the pressure in the dressing room is 10Pa,the pressure in the second undressed room is-5Pa,the pressure in the first undressing room is-25Pa,the air quantity of each room is the minimum.The air change rate is 22.9h-1 in the dressing room,3.4h-1 in the protective clothing dressing room,6.9h-1 in the first undressing room,4.2h-1 in the first undressing room.

combination of normal time with epidemic periodventilation systemhygiene passing througheffect of differential pressure

林劲松、乔静、黄凯新、李照龙、李建敏、王瑞强

展开 >

中国建筑第七工程局有限公司 郑州 450004

中建中原建筑设计院有限公司 郑州 450004

中国电子工程设计院股份有限公司 北京 100142

平疫结合 通风系统 卫生通过 压差影响

中建七局基金项目

CSCEC7b-2022-Z-26

2024

制冷与空调(四川)
四川省制冷学会 西南交通大学

制冷与空调(四川)

CSTPCD
影响因子:0.475
ISSN:1671-6612
年,卷(期):2024.38(1)
  • 11